Air Tightness Test of existing apartments

Project Description

The apartment block was built in 2005 and is constructed of reinforced concrete with external EPS insulation. The clients are experiencing poor air quality, propagation of mould growth and high levels of condensation forming on the window panes during the winter months.

A permeability of 0.783 m3/hr/m2 at 50 pa was identified during the air tightness blower door test of sample apartments.

Research published by the Scottish Government indicates that infiltration rates lower than 3 m3/hr/m2 @ 50 Pa are likely to result in air quality and condensation problems unless a ‘designed whole house ventilation system (input and extract)’ is present. Ref: Sound and Air testing, Scottish Government (2015)

Based on the results of the air tightness test it can be assumed that a fit or purpose ventilation strategy was not employed during the design of these apartments. With the result occupants have to open their windows to ventilate their apartemnts leading to high heat loses during the winter months.
It can be concluded that if a well-designed mechanical ventilation system had been installed when the apartments were initially built that residents would not be facing their current issues as mentioned above. The residents are currenlty investigating the possibilities to improve the ventilation of their apartments including replacing their current windows with ones that have trickle vents or the option of retrofitting decentralised mechanical ventilation systems in each apartment.

1 Sound and Air testing, Scottish Government (2015):-
https://www.webarchive.org.uk/wayback/archive/20170703102848/http://www.gov.scot/Topics/Built-Environment/Building/Building-standards/soundairtesting

Project Details

  • Couronnes d’Arbres

  • Switzerland

  • Private Client

  • Passive House

  • Concept/planning

Project Gallery

Floor Plan

Air Testing Switzerland Floor Plan

retrotec License

retrotec license
Contact Us

Need an Air Tightness Test?

If you require Air Tightness Testing for your Commercial or Residential property, please contact AiroTech for a quotation or to discuss your requirements.

Contact Us